Installation & Code Compliance

Lumiere Studio products are intended for installation by qualified professionals. This page summarizes the installer's responsibilities. Product-specific limits are on each product's spec sheet in Downloads.

Installer responsibility

The installer is solely responsible for ensuring that the lighting design and installation comply with the National Electrical Code (NEC), all applicable local codes, and the requirements of the Authority Having Jurisdiction (AHJ). Permit and inspection requirements are set by the local AHJ.

Class 2 power limits

Class 2 wiring methods (NEC Articles 411 and 725) apply only when products are supplied by a power source that is listed and marked Class 2. A Class 2 power source is limited to 100 VA per output, which is 96 W on a 24V output. Output wiring from a power source that is not marked Class 2 must use the wiring methods the NEC requires for that circuit. Each Lumiere Studio spec sheet lists the NEC class of every recommended driver and how much tape fits on one 96 W Class 2 output.

Run lengths and loads

  • Do not exceed the maximum run length per power feed or the loads stated on the product spec sheet.
  • Size each driver so the connected load is at or below 80% of its rated output.
  • Never connect low-voltage tape light directly to line voltage.
  • Keep drivers and controllers in serviceable, ventilated locations rated for the environment (dry, damp or wet).

Limitation of responsibility

Lumiere Studio is not responsible for improper installation, code non-compliance, or any resulting damage. Products installed outside their published specifications or contrary to these requirements are not covered by the Lumiere Studio warranty.

Questions? Contact us at info@lumierestudio.com or 386-732-3131.